Appendix D: SNMP MIBS
ManageUPSNET User Instruction Manual 51
upsAlarm Group
(continued)
upsAlarmBypassBad Not applicable.
upsAlarmOutputOffAsRequested Confirmation.
upsAlarmUpsOffAsRequested Confirmation.
upsAlarmChargerFailed Battery charger has failed or its fuse has blown.
upsAlarmUpsOutputOff Confirmation, persistent until output is turned on.
upsAlarmUpsSystemOff UPS shutdown.
upsAlarmFanFailure Not supported.
upsAlarmFuseFailure Input circuit breaker is open or charger fuse has blown.
upsAlarmGeneralFault A UPS fault was detected that is not specifically defined in the
standard MIB.
upsAlarmDiagnosticTestFailed A user initiated test has failed.
upsAlarmCommunicationsLost Lost Serial Communications with the UPS.
upsAlarmAwaitingPower Not supported.
upsAlarmShutdownPending A shutdown timer has begun counting.
upsAlarmShutdownImminent Output shutdown will occur in approximately 5 seconds.
upsAlarmTestInProgress A user requested UPS test has begun.
upsTest Group
upsTestId SET this object to the Object Identifier (OID) of the test you want to
run.
upsTestSpinLock In order to initiate a UPS test, you must use the upsTestSpinLock
as follows: First: GET (read) the current integer value of
upsTestSpinLock. Next: SET (write) the integer value just read
back to the upsTestSpinLock object and SET upsTestId to the OID
of the test you wish to run. It is required that the two SET
operations be performed in the same SNMP packet. The purpose
of the upsTestSpinLock object is to eliminate the possibility of two
Managers simultaneously initiating tests on the same Agent. See
the MIB description for more information.
upsTestResultsSummary All valid MIB results are supported. The result of the last test run
will be remain in this object.
upsTestResultsDetail If upsTestResultsSummary report doneWarning(2), doneError(3)
or aborted(4), then this object will contain a message string
detailing more information about the test failure.
upsTestStartTime The value of sysUpTime when the UPS test was initiated.
Table 7. RFC1628 Support (Continued)