Appendix D: SNMP MIBS
ManageUPSNET User Instruction Manual 55
ONEAC Private
Extension MIB
This section details information about
ONEAC’s Private Extensions UPS MIB. This
MIB is also provided in the SNMP Agent and
use of it is optional. ONEACXT.MIB is the
name of this MIB and it is found in the MIBS
directory on the ONEAC SNMP Diskette.
NOTE: This information is in addition to the
descriptions provided in the MIB.
Table 8. Private Extension MIB
oneacUpsIdent Group
NOTE: The objects in this group are read-only and are provided so that the
Network manageability adapter can be fully identified via the network.
oneacUpsSNMPInterfaceModel This object identifies the Model of the Interface.
Example: AK-SNMP-NE
oneacUpsSNMPInterfaceDateCode Year/Week date of manufacture code
Example: 9710 (1997, Week 10)
oneacUpsSNMPInterfaceSerialNo Unique serial number of the interface.
oneacUpsAgentBuildDate Date at which the ManageUPS
NET
Firmware was compiled.
oneacUpsAgentBuildTime Time at which the ManageUPS
NET
Firmware was compiled.
oneacUpsDateCode The date of manufacture for the UPS in the form of yymmdd.
oneacUpsSerialNo The serial number of the UPS
oneacUpsName A 12 character name UPS name stored on the UPS itself.
oneacUpsControl Group
oneacUpsControlNotifyDelay The number of seconds the UPS waits after detecting a
power failure before any notification occurs.
oneacUpsControlOffOn Any positive value written to this object will cause the UPS to
be reset in the same manner as if the front panel switch was
turned off and then back on. This can be used in situations
where a manual restart is required.
oneacUpsControlPwrFailSim Any positive value written to this object will cause the UPS to
go on battery power for about 15 seconds.